   Andrew Gabriel to operator jay   
   Re: Easy/best way to rewire bathroom lig   
   07 Feb 14 10:06:34   
   
   From: andrew@cucumber.demon.co.uk   
      
   In article <52f36911$0$17163$c3e8da3$dd9697d2@news.astraweb.com>,   
   	"operator jay"  writes:   
   >   
   > I agree with the you and disagree with the the other poster about putting a   
   > JB inside a wall.  I guess it may be a matter of jurisdiction.  In the   
   > locations that I know of, a JB must remain accessible and drywalling over a   
   > box is not considered accessible.   
      
   In the UK, if connections will become inaccessible, they must be made   
   by crimps, brazing, or soldering, i.e. long-life permanent maintenance-   
   free methods which are not compromised by any expectation of being able   
   to dissassemble/reassemble in the future, as they will be inaccessible.   
      
   Furthermore, the hidden cable location (and hence the hidden connection)   
   must be in an expected location, such as in a horizontal or vertical   
   line from a visible wiring accessory, or within a few inches of a   
   corner or the top of the wall, or it must be > 2" deep in the wall, or   
   protected by a steel plate in the wall.   
      
   --   
   Andrew Gabriel   
   [email address is not usable -- followup in the newsgroup]   
      