   Re: Function of Portable Generator Outle   
   07 Jan 19 12:18:37   
   
   From: arl_123234@hotmail.com   
      
   On 1/7/19 11:12 AM, gfretwell@aol.com wrote:   
      
   > If the neutral was not bonded and you did have a short to the EGC, I   
   > still do not see the fault path, even in the frame was grounded.   
   >   
      
   Hello, and that's because in that case there wouldn't be a fault path   
   with a floating/unbonded neutral (not counting capacitive coupling,   
   which is presumed to be inconsequential (but can be an issue on Navy   
   ships, but that's another story).  Sincerely,   
      
      
   --   