Forums before death by AOL, social media and spammers... "We can't have nice things"
|    comp.dcom.telecom    |    Telecommunications digest. (Moderated)    |    17,262 messages    |
[   << oldest   |   < older   |   list   |   newer >   |   newest >>   ]
|    Message 15,441 of 17,262    |
|    Eric Tappert to All    |
|    CO backup power [telecom]    |
|    09 Oct 20 13:20:36    |
      From: tappert@ieee.org              Bob,              I don't know what the current standard is, but the "old Bell System"       guidance for central offices was 8 hours of battery, standby generator       with 24 hours of fuel in the day tank and a week's worth of fuel       on-site. A few years ago the FCC issued a ruling that required COs to       have 24 hours of backup power and cell sites 8 hours. That was the       first federal guidance on the issue and was issued in response to       hurricane Katrina and the fact that first responders were using cell       phones for communication. With the vastly expanded number of cell       sites required for 5G, I don't know if the rule still is in force.              Hope this helps.              Eric Tappert              --- SoupGate-Win32 v1.05        * Origin: you cannot sedate... all the things you hate (1:229/2)    |
[   << oldest   |   < older   |   list   |   newer >   |   newest >>   ]